Troubleshooting
Common issues and fixes for the IRIV IO Controller.
It is a microcontroller
The IRIV IO Controller runs on a Raspberry Pi RP2350A microcontroller. It has no Linux, Raspberry Pi OS or Node-RED. If a guide tells you to SSH in or run sudo, it is for a different IRIV product.
Power
Unit does not power up
- Check the supply: Terminal 1 needs 10–30 V DC on V+ and V- (not DGND). USB-C needs 4.9–5.2 V.
- PTC has opened: the power input is protected by a 500 mA resettable PTC. After a surge or overcurrent it can open. Remove power, let it cool for a few minutes, and try again.
- If it still does not power up, contact support@cytron.io.
Uploading Firmware
Board does not appear as a USB drive
- Use a USB-C cable that carries data (some cables are charge-only).
- Hold BOOT, press and release RESET, then release BOOT. Both are pinhole buttons — use a paperclip.
- A drive should appear. Copy the UF2 file (for example the CircuitPython build) onto it; the board reboots by itself.
Digital Inputs
Sensor does not trigger a DI
- Check the group's S/S polarity. PNP sensors need S/S to the supply −; NPN sensors need S/S to the supply +.
- Check the right S/S. DI0–DI4 use S/S0..4 on Terminal 1; DI5–DI10 use S/S5..10 on Terminal 2. Each group can be PNP or NPN independently.
- Dry contacts (switches, relay contacts) go between DIx and DGND, not S/S. The built-in isolated supply powers them.
- Signal level: high must be at least 3 V; low must be below 0.8 V.
- Fast pulses: the inputs are rated to 5000 Hz at 50% duty cycle.
Digital Outputs
Load does not switch
- The outputs are dry-contact solid-state relays. They do not supply voltage: wire the load and its own supply in series across the two DO contacts.
- Maximum 50 V and 500 mA per channel, DC or AC.
Electrical noise when switching relays
Fit a flyback diode across the relay coil (or other inductive load). The outputs have built-in surge protection, but the diode reduces EMI.
Analog Inputs
Readings are wrong or stuck
- Check that channel's AN-IN MODE switch on the bottom panel: voltage mode (0–10.56 V) or current mode (0–42.58 mA, switch ON). AN0 and AN1 have separate switches.
- Scaling: in voltage mode the ADC pin sees AN × 5/16, so 10.56 V reads as full scale.
- CircuitPython:
analogio.AnalogIn.valueis scaled to 0–65535 even though the ADC is 12-bit. - Ground: the analog inputs are not isolated — AGND is the system ground. Avoid ground loops with sensors powered from another supply.
RS485
No communication or errors on long buses
- Swap-check A and B, and wire G as well as A/B for noise immunity.
- Turn the RS485 R-Term DIP switch ON only on the first and last device of the bus.
- Match baud rate and serial settings (maximum 500 kbps).
- In your own firmware, RS485 is UART1: TX = GP24, RX = GP25. Direction control is automatic, so there is no DE/RE pin.
Modbus slave ID or baud rate unknown
Cytron's Modbus Configuration Tool tutorial shows how to set the slave ID and baud rate. The default firmware and its register map are not in the datasheet — ask Cytron support if you need them.
Ethernet
No network link
- The RJ45 is a 10/100 W5500 controller on SPI0 (MOSI GP19, MISO GP20, SCK GP22, CSn GP21, INT GP18, RESET GP23). Use these pins when initialising it in your code.
- Check the cable and that your firmware brings the W5500 out of reset.
Clock
Time is lost after power-off
Insert a CR2032 coin cell in the RTC holder (PCF85063A, I2C0 at 0x51 on GP16/GP17). The cell is fitted by the user.