Troubleshooting

Common issues and fixes for the IRIV IO Controller.

It is a microcontroller

The IRIV IO Controller runs on a Raspberry Pi RP2350A microcontroller. It has no Linux, Raspberry Pi OS or Node-RED. If a guide tells you to SSH in or run sudo, it is for a different IRIV product.

Power​

Unit does not power up​

  1. Check the supply: Terminal 1 needs 10–30 V DC on V+ and V- (not DGND). USB-C needs 4.9–5.2 V.
  2. PTC has opened: the power input is protected by a 500 mA resettable PTC. After a surge or overcurrent it can open. Remove power, let it cool for a few minutes, and try again.
  3. If it still does not power up, contact support@cytron.io.

Uploading Firmware​

Board does not appear as a USB drive​

  1. Use a USB-C cable that carries data (some cables are charge-only).
  2. Hold BOOT, press and release RESET, then release BOOT. Both are pinhole buttons — use a paperclip.
  3. A drive should appear. Copy the UF2 file (for example the CircuitPython build) onto it; the board reboots by itself.

Digital Inputs​

Sensor does not trigger a DI​

  • Check the group's S/S polarity. PNP sensors need S/S to the supply −; NPN sensors need S/S to the supply +.
  • Check the right S/S. DI0–DI4 use S/S0..4 on Terminal 1; DI5–DI10 use S/S5..10 on Terminal 2. Each group can be PNP or NPN independently.
  • Dry contacts (switches, relay contacts) go between DIx and DGND, not S/S. The built-in isolated supply powers them.
  • Signal level: high must be at least 3 V; low must be below 0.8 V.
  • Fast pulses: the inputs are rated to 5000 Hz at 50% duty cycle.

Digital Outputs​

Load does not switch​

  • The outputs are dry-contact solid-state relays. They do not supply voltage: wire the load and its own supply in series across the two DO contacts.
  • Maximum 50 V and 500 mA per channel, DC or AC.

Electrical noise when switching relays​

Fit a flyback diode across the relay coil (or other inductive load). The outputs have built-in surge protection, but the diode reduces EMI.

Analog Inputs​

Readings are wrong or stuck​

  • Check that channel's AN-IN MODE switch on the bottom panel: voltage mode (0–10.56 V) or current mode (0–42.58 mA, switch ON). AN0 and AN1 have separate switches.
  • Scaling: in voltage mode the ADC pin sees AN × 5/16, so 10.56 V reads as full scale.
  • CircuitPython: analogio.AnalogIn.value is scaled to 0–65535 even though the ADC is 12-bit.
  • Ground: the analog inputs are not isolated — AGND is the system ground. Avoid ground loops with sensors powered from another supply.

RS485​

No communication or errors on long buses​

  • Swap-check A and B, and wire G as well as A/B for noise immunity.
  • Turn the RS485 R-Term DIP switch ON only on the first and last device of the bus.
  • Match baud rate and serial settings (maximum 500 kbps).
  • In your own firmware, RS485 is UART1: TX = GP24, RX = GP25. Direction control is automatic, so there is no DE/RE pin.

Modbus slave ID or baud rate unknown​

Cytron's Modbus Configuration Tool tutorial shows how to set the slave ID and baud rate. The default firmware and its register map are not in the datasheet — ask Cytron support if you need them.

Ethernet​

  • The RJ45 is a 10/100 W5500 controller on SPI0 (MOSI GP19, MISO GP20, SCK GP22, CSn GP21, INT GP18, RESET GP23). Use these pins when initialising it in your code.
  • Check the cable and that your firmware brings the W5500 out of reset.

Clock​

Time is lost after power-off​

Insert a CR2032 coin cell in the RTC holder (PCF85063A, I2C0 at 0x51 on GP16/GP17). The cell is fitted by the user.


Source(s):

  • IRIV IO Controller Datasheet, Rev 1.0, July 2024
  • Cytron Knowledge Base, IRIV IO Controller verified reference (Oct 2026)