Skip to main content

IRIV IOC MQTT Gateway

IRIV IOC MQTT Gateway

Product page · Getting Started series (6 parts)

The IRIV IOC MQTT Gateway is the same hardware as the IRIV IO Controller, preloaded at the factory with Cytron's MQTT Gateway firmware. It publishes the digital inputs, analog inputs and Modbus RTU (RS485) readings to your MQTT broker over Ethernet, and lets you switch the digital outputs from MQTT — all set up from a web page, with no coding.

Hardware, terminals, wiring and electrical limits are identical to the IRIV IO Controller: see Hardware Layout and I/O Reference.

Do not overwrite the firmware

Do not flash CircuitPython or other firmware on this unit. The MQTT Gateway firmware is licensed to the unit's CPU ID. To update it, use only Cytron's .uf2 files (see below).

How It Differs from the IRIV IO Controller​

ItemIOC MQTT GatewayIRIV IO Controller
FirmwarePreloaded MQTT Gateway firmwareYou program it (e.g. CircuitPython)
USB-CConfiguration (and power)Programming and configuration
User button (GP28)Factory resetProgrammable
USR LED (GP29)Network / MQTT statusProgrammable
BuzzerBeeps on factory resetProgrammable
RTCFitted but not used by the firmwareUsable
DatasheetRev 1.0, June 2026Rev 1.0, July 2024

MQTT​

  • Standard MQTT on port 1883. There is no TLS/SSL on the device — for encrypted cloud links, send the data through a local secure broker or edge gateway.
  • Topics are built on a Base Topic (for example iriv/CB62/): di/…, ai/…, do/…/cmd, do/…/state, mbpoll/…, mbwrite/…, mbwrite/…/confirm.
  • QoS 0/1/2 and Retain can be set per channel.

What You Can Configure​

ChannelsOptions
Digital inputs DI0–DI10Enable, rename, publish On Change / Periodic / Both (period ≥ 1 s), topic, QoS, Retain
Digital outputs DO0–DO3Enable, rename, startup state ON/OFF, command topic (1/ON or 0/OFF), state topic published on change
Analog inputs AI0–AI10–10V or 4–20mA sensors, periodic publish (≥ 1 s)
RS485 Modbus RTU master1200–115200 baud, parity, stop bits, timeout; up to 32 poll jobs (slave 1–247, FC1/2/3/4, Int16/UInt16/Int32/Float32, byte order, scale and offset); write jobs FC5/FC6/FC16 from an MQTT topic with confirmation
DiagnosticsDashboard (uptime, free memory, live I/O), Test Publish, manual Modbus register read

USR LED Status​

PatternMeaning
Slow blinkEthernet down
Solid onEthernet up, MQTT disabled
One pulse every 1.5 sMQTT enabled but broker not reachable
Two pulses every 3 sMQTT connected

Factory Reset​

Hold the USER button while powering on (or press RESET while holding USER) for about 10 seconds, until the buzzer beeps. This clears the broker, I/O, poll and write settings — back them up first. The firmware licence is kept.

Firmware Update​

  1. Normal: web interface → System → Firmware Update → upload the Cytron .uf2 from the product page's firmware folder.
  2. Recovery: hold BOOT, connect USB-C (PROG), and copy the Cytron .uf2 to the "RP2350" drive.

If Windows 11 no longer recognises the unit over USB after Windows Update KB5124008, update to the latest firmware.

Tutorials​

Getting Started with IRIV-IOC MQTT Gateway — 6 parts: broker connection, I/O channels, RS485 / Modbus RTU, diagnostics and system settings, factory reset and firmware update.


Source(s):

  • IRIV IOC MQTT Gateway Datasheet, Rev 1.0, June 2026
  • IRIV IOC MQTT Gateway product page (my.cytron.io), read Oct 2026
  • Cytron tutorial series: Getting Started with IRIV-IOC MQTT Gateway (Jun 2026)